From watts to a copper wire size you can talk about
Household cable sizing starts with current. In single-phase power, current in amperes is watts divided by (voltage × power factor). At the default 2,000 W geyser on 230 V with a power factor of 1, I = 2000 ÷ 230 = 8.70 A. This page then multiplies by 1.25 to leave a simple margin (10.87 A) and picks the smallest copper size in a short domestic table whose current ratings are at least that design current: 1.5 mm² ~ 15 A, 2.5 mm² ~ 20 A, 4 mm² ~ 27 A, 6 mm² ~ 35 A, 10 mm² ~ 46 A, 16 mm² ~ 62 A. For the geyser, 1.5 mm² would carry the current on paper, but many Indian houses still run geysers and ACs on 2.5 mm² or 4 mm² because of length, grouping and future load — which is why the card also prints a voltage-drop sketch.
Voltage drop
A long, thin cable wastes volts as heat. A common estimating formula for single-phase go-and-return drop is 2 × I × L × r / 1,000, where L is the one-way length in metres and r is resistance in ohms per kilometre. Using about 12.1 Ω/km for 1.5 mm² copper, a 15 m run at 8.70 A drops 2 × 8.70 × 15 × 12.1 / 1000 = 3.16 V, about 1.4% of 230 V. That is usually acceptable. The same current on a 40 m run would be closer to 3.6% and might push you up a size. The resistances used here are typical annealed-copper figures; your cable’s data sheet wins if it disagrees.
| Load at 230 V | Current | Smallest table size after ×1.25 |
|---|---|---|
| 1,000 W | 4.35 A | 1.5 mm² |
| 2,000 W (default) | 8.70 A | 1.5 mm² |
| 3,000 W | 13.04 A | 2.5 mm² |
Hindi mein
2,000 वाट, 230 वोल्ट: 8.70 एम्पीयर। 1.25 का मार्जिन लगाने पर 10.87 एम्पीयर, इस घरेलू तालिका में 1.5 मिमी² काफी है। लंबी लाइन पर वोल्टेज ड्रॉप देखें — 15 मीटर पर लगभग 3.2 वोल्ट। यह इलेक्ट्रीशियन की डिज़ाइन नहीं है।
What this page refuses to pretend
It does not know how many circuits share a conduit, how hot the roof void is, or whether the load is a motor that starts at several times its running current. Those factors live in IS 3961 / manufacturer tables and in an electrician’s judgement. Treat the suggestion as a way to understand a quotation, not as permission to rewire a house from a webpage. For LED lighting circuits 1.5 mm² is common; for 1.5-ton AC points many electricians prefer 2.5 or 4 mm² regardless of the tidy 6–7 A running current, because of starting current and future replacement machines.
How to use
- Type the watts of one circuit, not the whole house, unless you really mean the incomer.
- Leave 230 V unless you measured something else.
- Set length as the one-way run from the board to the point.
- Read current, suggested size and voltage drop, then confirm with an electrician and the cable maker’s table.
I = P / (V × pf) is the single-phase power identity. The current-rating column is a simplified clipped-copper domestic set for estimating, aligned with common Indian site tables, not a full copy of any one manufacturer’s chart. Voltage-drop resistances are typical copper Ω/km values. Follow IS wiring practice and a licensed electrician for anything that will be energised.
A 1.5-ton AC example
A 1.5-ton air-conditioner may run around 1,200–1,800 W. At 1,500 W the current is 6.52 A, and the table would allow 1.5 mm² after the 1.25 margin. Many electricians still pull 2.5 mm² or 4 mm² to that point because the compressor’s starting current is several times higher and because the next owner may install a larger machine on the same wires. The calculator will not override that habit; it will only show you the running-current arithmetic so you understand the quotation.